AMERICAN ALLERGY SUPPLY HOME PAGE | IAQ

Air Quality in the Doctors Office Part 1

Professional Office Building IAQ Study

Allergist Waiting Area

Waiting Area Memorial Hermann SW Hospital Houston TX

Most Professional Office Buildings are located near a Busy Street, Highway, or Freeway.

Traffic seen through the doctor's office window Bellaire and Loop 610

Traffic seen through the doctor's office window

Particulate Matter (PM2.5) Air Pollution from a METRO Bus

Particulate Matter (PM2.5) Air Pollution near the Doctor's Office is caused by Auto and Truck traffic. The greatest concentration of outdoor air pollution PM 2.5 occurs between 8:30 am and 9:00 am each morning when people drive to work.

The Flags shows that the prevailing winds blow the Freeway Air Pollution in the direction of the office building.

prevailing winds blow the Freeway Air Pollution in the direction of the office building

How does Outdoor Air Pollution Enter the Building

Outdoor Air Pollution enters the building through the front and rear entrance doors.

State Laws requires outdoor air be brought into the building through an air duct to dilute the CO & CO2 gasses. This fresh air - makeup air represents 10%-20% of all the air in the building. It takes the building MERV 7 air filters 1 - 3 hours to filter the >0.5 micron particle from the morning auto emissions.

This automatic door opener keeps the door open for 20 seconds.

This automatic door opener keeps the door open for 20 seconds. Opening this door brings in the car pollution into the building.

Normally building engineers are more concerned about hot humid air being brought into the building than air pollution.

Positive Air Pressure at the Front Door

Positive air pressure at the front door prevents the outdoor air pollution from coming into the building. Tested here with tissue paper. This occurs when the air conditioning / heating system is ON.

Positive air pressure at the front door prevents the outdoor air pollution from coming into the building.

Negative Air Pressure at the Front Door

Negative pressure at the front door sucks the outdoor air pollution into the building. In just 20 seconds, the indoor air near the door gets twice as dirty. This occurs when the air conditioning / heating system is OFF.

When the front door and the rear door of this building are open the air tunnels through the building. A lot of air pollution is sucked into the building.

This Delivery Man keeps the front door open.

This Delivery Man keeps the front door open. He leaves his truck idleing while he is in the building.

Patients park in the front of the building and enter through the front door

100's of Allergy Patients park in the front of the building and enter through the front door for quick 20 minute allergy shots during the day.

Allergy Patients park in the front of the building

Houston TX Allergy Clinic Waiting Area Indoor Air Quality

Houston TX Allergy Clinic

Those working near freeways breathe the dirtiest air from cars and diesel trucks.

The EPA has an Outdoor Air Monitor near the Allergy Clinic measuring PM 2.5 particles. About 10 days each month the Outdoor Air Quality is pretty bad and the PM2.5 is about 15 micrograms / m3.

Today's Texas Air Quality Forecast

http://www.tceq.state.tx.us/compliance/monitoring/air/monops/forecast_today.html

EPA PM2.5 monitor station Houston, TX

Texas Air Quality PM 2.5

Find out how Clean the Air is at your Clinic http://www.scorecard.org/

About 10 days each month the Outdoor Air Quality is pretty bad

There is a direct relationship between the outdoor air quality PM2.5 and the >0.5 micron particles/ft3 particle count in the Allergy Clinic Waiting Area.

MERV 7 Building Air Filters are 10% efficient on >0.5 micron particles.

The Building uses a MERV 7 Polyester - Link Air Filter.

This filter is 40% efficient on particles >1.0 microns. My test data shows that the air filters performed good to excellent even when the air pollution was very high outdoors.

This MERV 7 air filter protects the air conditioning equipment not your lungs.

*

fiberbond_poly_panel.jpg (5928 bytes)

MERV 7 Poly-Link Polyester Air Filters

MERV 7 Poly-Link Polyester Air Filters used in most commercial air conditioning systems.
polypanel_efficiency_chart.jpg (81112 bytes) This graph shows that the  MERV 7 Poly-Link Polyester Air Filters used in most commercial air conditioning systems are 40% efficient on >1.0 micron particles and only 10% efficient on >0.5 micron size particles.

It takes the building MERV 7 air filters 1 - 3 hours to filter the >0.5 micron particle from the morning auto emissions.

This MERV 7 air filter is designed to protect the AC equipment not your lungs.

*

asthma-trigger.jpg (35183 bytes)
Aerodynamic Diameter (micron)

> 9.0

6.0 to 9.0

4.6 to 6.0

3.3 to 4.6

2.15 to 3.3

0.41 micron to 2.15 micron

Likely Region of Deposit

Filtered by nose

Pharynx

Trachea / Primary Bronchi

Secondary Bronchi

Terminal Bronchi

Alveoli        

Problem to Address

Allergy Clinic needs a better building air filter MERV 8 / 11 or a  portable room air cleaner for those 10 days out of the month when the car emissions from the outdoor air pollution is high. When the building’s air filters do not remove the particles from the air,
the occupant’s lungs become the filter.

POOR OUTDOOR AIR QUALITY Outdoor Air Quality is 1,000,900 particles / ft3 > 0.5 micron size
TUESDAY 4/22/2008 POOR OUTDOOR AIR QUALITY

Outdoors a 12 year old child would breath in 10,009 asthma trigger particles in each breath @ >0.5 microns reaching the Alveoli.

Reading 10009 x 100 = Outdoor Air Quality is 1,000,900 particles / ft3 > 0.5 micron size

The data shows that on >0.5 microns lung damaging dust size particles that the air quality in the doctor's office was Poor to Fair Monday through Friday.

The data shows that on Saturday with very little traffic the >0.5 microns air quality in the doctor's office was Very Good.

POOR Indoor Air Quality TUESDAY 4/22/2008

POOR Indoor Air Quality

Waiting Area

Reading 1533 x 100 = 153,300 particles/ft3 @ >0.5 MICRON

VERY GOOD Indoor Air Quality SATURDAY 4/26/2008

(No car traffic)

VERY GOOD Indoor Air Quality

Waiting Area

Reading 137 x 100 = 13,700 particles/ft3 @ >0.5 MICRON

*

IAQ-HOUSTON-APRIL-2008.jpg (64704 bytes)

Houston TX Allergy Clinic Waiting Area Air was tested Monday through Saturday at ~ 9:00 AM.

There is a direct relationship between Higher Outdoor Pollution and Higher Indoor Pollution for Particles >0.5 Micron in size.          

*

Indoor Air Quality Data for Houston TX Allergy Clinic

>0.5 micron particles / ft3 &

>1.0 micron particles / ft3

DAY IAQ RATING MONDAY 4/21/2008 TUESDAY 4/22/2008 WEDNESDAY 4/23/2008 THURSDAY 4/24/2008 FRIDAY 4/25/2008 SATURDAY 4/26/2008
INDOOR AIR QUALITY

@ >0.5 MICRON

LUNG DAMAGING DUST

point-5-micron-1.jpg (18622 bytes) FAIR-POOR IAQ

99,000 @ >0.5 MICRON

POOR IAQ

153,300 @ >0.5 MICRON

FAIR IAQ

89,700 @ >0.5 MICRON

FAIR IAQ

41,100 @ >0.5 MICRON

FAIR IAQ

54,800 @ >0.5 MICRON

VERY GOOD

13,700 @ >0.5 MICRON

INDOOR AIR QUALITY

@ >1.0 MICRON

1-MICRON.JPG (20163 bytes) VERY GOOD

3100 @ >1.0 MICRON

 

GOOD

7600@ >1.0 MICRON

EXCELLENT

2100 @ >1.0 MICRON

VERY GOOD

2900 @ >1.0 MICRON

VERY GOOD

4600 @ >1.0 MICRON

EXCELLENT

1000 @ >1.0 MICRON

Indoor Air Quality in the Doctor's Office Part 2

AMERICAN ALLERGY SUPPLY HOME PAGE | IAQ

06/01/2008